Permit: T04CM04885

Parcel: 117120010


Addresses:

110 E PENNINGTON ST


Inspection Status: Approved

Inspection History: BUILDING PRE-SLAB

Permit Number - T04CM04885

Inspection Description - BUILDING PRE-SLAB

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2005 BUILDING PRE-SLAB Approved IVRS - Inspection :*
07/21/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*
1) ENTRY SLABS AT WEST OK
06/20/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* FOOTING FOR WINDOW WALLS 1-7 OK
06/09/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* TOP OF EACH BASIN OK.
06/06/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* CATCH BASIN WALLS TO TOP
06/02/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* PARTIAL A-B/4-12
05/25/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*
1) P; B-B.7/7-11 SOG OK
05/20/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*
1) CATCH BASIN WALLS AND BASE
05/18/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* LEVEL 2 6-10 OK TO POUR WHEN SP INSP CONFIRMS REPAIR NOTED BELOW. 1) DO NOT RUN FELT PAPER OVER RABBIT EARS ( LINE9, LINE 10). 2) SPACE CHORD STEEL 3" O.C AND TIE DOWN AS NECESSARY.
05/17/2005 BUILDING PRE-SLAB Not ready for Inspection IVRS - Inspection :*
05/16/2005 BUILDING PRE-SLAB Not ready for Inspection IVRS - Inspection :* 1) DETAIL PROVIDED DOES NOT SHOW HOW THICK WALLS ARE. 2) REBAR REQUIRES 1 1/2" CLEAR FROM FROM AND 3" CLEAR FORM DIRT.
05/12/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* ALL TOPPING SLAB OK TO PLACE. NOTE: BOTH MYSELF AND SPECIAL INSPECTOR MISIDENTIFIED LEVEL 5 AS LEVEL 4 ON 4/15/05. THE EXTRA CHORD STEEL ON LINE A IS ACTUALLY IN LEVEL 6 ( WE ALSO MISIDENTIFIED LEVEL 6 AS LEVEL 5) ALL STEEL IS CORRECT OR THERE IS EXTRA ON ALL TOPPING SLABS
05/11/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*DENIED 1) 10 EACH #5 CHORD BARS REQUIRED ALONG LINE A LEVEL 5. 2) AT LEVEL 6-7 USE LEVEL 7 DETAIL @ LINE 9
05/09/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*
05/06/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*LEVEL 3-4/6-10 AND LEVEL 4-5 /6-10 OK TO PLACE CONCRETE.
05/05/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* TOPPING SLAB LEVEL 2-3/AREA 6-10 OK TO PLACE WHEN SPECIAL INSPECTOR CONFIRMS 1) ADDITION 2 EACH 8' CHORD BAR EXTENSIONS @ B -12. 2) UNTWIST OVERLAPPED CHORD STELL @ B-12. 3) PULL " RABBIT EAR" EMBEDS OFF DECK AS NECESSARY TO ENSURE PROPER CONCRETE FLOW AROUND EARS TO BOND TO EMBEDS.
05/02/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* RAMP UP OK AND STAIR N SIDE OF RAMP OK.
04/27/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* SEE YESTERDAYS NOTES
04/26/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* LEVEL 7 F.O ELEVATOR & SHOP S.O.G
04/22/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* PRESLAB- LEVEL 1 AREA A-B/3-S?? OK
04/19/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* SEE YESTERDAY
04/18/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* LEVEL 4 AREA 1-6 AND LEVEL 2 AREA 1-6
04/11/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*
04/08/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :*
04/06/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* LEVEL 6 AREA 1-6 OK TO POUR. PLEASE TIE DRAG & CH?? BARS @ 3" O,C. BEFORE POUR. PLEASE HAE THEM SPACED & TIED FOR SUBSEQUESNT INSPECTIONS.
03/30/2005 BUILDING PRE-SLAB Partial Approval IVRS - Inspection :* LEVEL 3 GRIDS 1-605/A-C TOPPING SLAB OK TO PLACE.