Date Description Inspector Results Comments
04/28/2005 BUILDING - FINAL Approved IVRS - Inspection :*
04/26/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SECURE CONDENSATE TO ROOF AT BLKS
2) CONDENSATE DRAINS INTO V.T.R. INCORRECT CONNECTION SEE DETAIL ABOVE
3) REMOVE OLD COOLER WIRING
4) FEED DRYER AND H20 HTR SEPERATELY, MOVE DISCONNECT AWAY FROM WALL SO COVER CAN BE OPENED EASIER
5) RECEPTACLE UNDER SINK LOOSE
6) 60 AMP FUSES IN ROOF A/C DISCONNECT AND TWO POLE 50 IN SERVICE ID A/C CIRCUIT WHITE WIRE AS A HOT WIRE BY COLOR
7) NEED TO LABEL IN SERVICE TWO COUNTER CIRCUITS, ALSO NEED DISPOSAL DISHWASHER CIRCUIT LABELED
8) FALSE COVER MISSING AT METER
9) LABEL SUB-PANEL FOR APT. IT SERVES