Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM04873
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/16/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* NEED FILTER AT OUTSIDE AIR INTAKES |
|
10/07/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*ROOF TOP -WEST SIDE- A. PLUG ELECT SWITCH AT REAR-KNOCK OUT REMOVED & NOT USED. B. REMOVE CONDENSATE P TRAP ( EXTERNAL) UNIT HAS BUILT IN TRAP. C. BLOCK AND CLAMPS PVC EVERY 4' ON & EAST SIDE UNIT. CUT 4"ABS SEWER VENT ON ROOF-BLOCKING ACCESS PANEL. PROVIDE OUTSIDE AIR AT ??. PROVIDE FLASHINGS AT ELECT. PENETRATION ON ROOF. |
|
10/03/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* NEED COMB ( LOWE DUCT) AIR WATER HTRS | |
09/28/2005 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :*CONNECT ELECTRICAL, GAS, CONDENSATE TO UNITS ON ROOF. |