Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/01/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BANDS ON FIRE WRAP ARE TOO LOOSE & MUST BE WITHIN ?? FROM EDGE. USE A BOND TENSION TOOL. DO NOT USE DIFFERENT BRANDS OF FIRE WRAPS. PROVIDE MIN 3" OVERLAP ON JOINTS. WRAP TO EXTEND ALL THE WAY TO TOP OF DUCT. NON COMBUSTIBLE MATERIAL ON WALL MUST EXTEND 18" ON ALL SIDES OF THE HOOD. SEE SECTION 507.9 IMC. SUPPORT ELECT CONDUIT TO EVAP COOLER. WIRE IS NOT AN APPROVED STRAP FOR CONDUIT. |