Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T04CM04868
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/16/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
01/24/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) PENDING MAS STRAP RETRO FIT |
|
01/13/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLUMBING AND ELECTRICAL NOT NAIL PROTECTED FROM OUTSIDE 2) MAS STRAP MISSING AT GARAGE |
|
01/12/2005 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) INSULATE CHANNELS 2) NAIL PROTECT PLUMBING AT ELECTRIC CONDUIT FROM OUTSIDE 3) MAS STRAP MISSING AT GARAGE ENTRY 4) MARK (DRH) SAID TO STOP INSPECTION |
|
01/10/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DBL STUDS REQUIRED UNDER GIRDER TRUSS NOTE 6/5 2) 5/D3 NAILING NOT PER PLAN. REMOVE DRYWALL NAILER 3) NO TRUSS DRAWINGS ON SITE 4) SHEARWALL #2 AT B/R MUST EXTEND TO TRUSS 5) REAR SHEAR NOT NAILED 6) OVERSPAN, STUD MISSING M/CLOSET 7) FRONT # SHEAR NOT NAILED 8) 2/D2 NOT COMPLIED WITH. ROOF NAIL NOT CHECKED 9) DOUBLE TOP PLATES REQUIRES SPLICE 48" SEPERATED |