Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2005 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 02/28/2005 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) 3 COAT LATH WITH 2 COAT WEEP SCREEDS. PLAN CALLS FOR 1 COAT 2) ELECTRIC SERVICE PLAN CALLS FOR 200 AMP MAIN, 400 AMP INSTALLED. DIAGRAM REQUIRED GROUNDING, GROUND TO FOLLOW NEUTRAL, RUN WIRE UP TO NEUTRAL BUSS 3) CONDUIT FROM NEW TO EXISTING OK TO COVER |