Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2005 | FIRE SPKLR - FINAL | Approved | ||
| 03/25/2005 | FIRE SPKLR - FINAL | Not ready for Inspection | 1.) BACK STOCK ROOM HEADS TO FAR OFF NORTHWALL 9' 6" . 7' 6" NEEDED. 2.) NEED AS BUILTS SHOWING CHANGES IN STOCK ROOM 3.) BACK EXIT CORRIDOR NEEDS SPRINKLER COVERAGE |
|
| 02/25/2005 | FIRE SPKLR - FINAL | Not ready for Inspection | Site inspection only OK to cover up. SITE ONLY. OK TO COVER UP. |