Permit: T04CM04847

Parcel: 136261290

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM04847

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
03/13/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCTS INSIDE THE BLDG MUST BE INSULATED WITH 1 1/2" DUCT LINES WITH MINIMUM R-5 VALVE
2) 1" DUCT LINER IS R4.2
3) NEED TO SEE DUCT SMOKE DETECTORS WIRED