Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T04CM04847
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2006 | PLUMBING - ROUGH, SOIL | Approved | ||
03/06/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4" GREASE WASTE INTO INTERCEPTOR 6" BUILDING DRAIN TO 6" BUILDING SEWER, TIES TOGETHER 6" DOWN STREAM OF INTERCEPTOR APP 5' WATER TEST INCLUDING 2" INTERCEPTOR VENT BACK INTO BUILDING OK PER RED LINE PLAN DATED 2/10/06 OWNERS CHANGES SHEET P2.1 1. PROVIDE GREEN TRACER WIRE WITH CONTINUATION OF 6" BUILDING SEWER WITH TEST AND REVISED APPROVED PLAN AT LATER DATE. |
|
03/03/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
02/09/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
11/02/2005 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*6" ABS DWV UNDER SLAB OK WATER TEST ONE RISER TO TEN FEET BATHROOM RE VENT INSTALLED GREASE WASTE STUBBED THROUGH EXTERIOR WALL ONLY: TWO PLACES OK TO COVER AS HIGHLIGHTED ON PLAN PLEASE CALL A PRE POUR INSPECTION |
|
11/01/2005 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) 4:45 FENCE LOCKED-NO ACCESS TO SITE, PLAN AND PERMIT |