Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 02/09/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE 3 SOUTH COLUMNS ANCHORS 2) S.E. HOLDOWN NOT CONNECTED TO FULL LENGTH DBL STUDS TWO EACH 3) PORCH POSTS NOT CLIPPED TO BOTTOM PLATE 4) GARAGE GLU LAM BEAM POSTS NOT CLIPPED. PROVIDE ENGINEERS APPROVED DETAIL 5) 7/SD3 NOT COMPLIED WITH 3 PLACES EAST WALL 6) 4/SD4 NOT COMPLIED WITH-NOT NAILED THRU ROOF 7) OSB DRAIN MUST BE PERPENDICULAR TO TRUSSES. ONE PANEL PARALLEL |
|
| 02/07/2005 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* |