Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM04823
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/16/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) HAVE CEILING FAN REMOVED FROM PLAN AND REPLACED WITH LIGHT ONLY AS FAN WAS TO LOW. HAVE PLAN REVISION APPROVED BY CITY OF TUCSON |
|
12/14/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CEILING FAN BLADES CANNOT BE BELOW 7'-0" 2) MUST USE CEILING FAN BOX LISTED FOR FANS 3) METAL CEILING FAN BOX MUST BE GROUNDED 4) USE OF DRYWALL SCREWS NOT ALLOWED FOR CEILING FAN BOX MOUNT. MINIMUM #10 SCREWS REQUIRED |