Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/02/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MC CABLE MUST BE SUPPORTED INDEPENDENT OF EMT, SEE NEC 300 2) STRAP MC WITHIN 8" OF BOXES 3) ISOLATE MC FROM COPPER WATER LINE ( ? LOCATION ) |