Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T04CM04804
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :*CORRECTIONS OK 65 PSI | |
10/27/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*ALL UNDERGROUND PIPING THAT IS BLK RION SHALL HAVE FACTORY APPLIED COATING SEE SECTION 1211.7 94 UPC ALL FITTINGS & TOOLD MARKS SHALL BE PRIMED THEN TAPED. PROVIDE 18" MINIMUM COVER FOR PLASTIC GAS PIPING UNDERGROUND |
|
06/07/2005 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* |