Permit: T04CM04804

Parcel: 12907006S


Addresses:

1563 E 36TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
11/15/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*CORRECTIONS OK 65 PSI
10/27/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*ALL UNDERGROUND PIPING THAT IS BLK RION SHALL HAVE FACTORY APPLIED COATING SEE SECTION 1211.7 94 UPC ALL FITTINGS & TOOLD MARKS SHALL BE PRIMED THEN TAPED. PROVIDE 18" MINIMUM COVER FOR PLASTIC GAS PIPING UNDERGROUND
06/07/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*