Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T04CM04804
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2005 | PLUMBING - YARD WTR LINE/TEST | Approved | 3" H20 CONNECTION TO BUILDING AT EXTERIOR OK | |
05/20/2005 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* 1) HYDROSTATIC PRESSURE TEST @ 105 PSI HAS BEEN HOLDING FOR 4 HRS. | |
05/09/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) PLEASE POST YOUR ADDRESS!! 2) 3" SCH 40 PVC YARDWATER WITH GALVANIZED RISERS AND CONNECTORS AT METER AND RPPBP ( 2" ) INSTALLED PER PLAN. 3) OK TO COVER SUBJ TO ARCHITECTS APPROVAL OF M?? TYPE. |