Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM04795

Parcel: 133452200


Addresses:

10255 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM04795

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
09/08/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH PREVIOUS ITEMS
09/07/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) COVERS FOR RECEPTACLES TO BE WEATHER PROOF WHETHER OR NOT PLUGED INTO 406.8
2) ENTRANCES ABOVE CURRENT CARRING PARTS TO USE APPROVED SEALING DEVICE
3) BOXES IN COMBUSTIBLES TO BE FLUSH 314.20
4) PLEASE PROVIDE ACCESS TO ATM MACHINE TO INSPECT CONNECTIONS, LISTING AND LABELING