Permit: T04CM04772

Parcel: 11005314C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T04CM04772

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) CITY APPROVED REVISED PLAN ON SITE 7/18/05
2) WILL NEED TO SEE WATER HEATER AREA AT FUTURE
08/05/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WATER TEST WASTE AND VENT SUB STERILE #132, #144 AND ROOM 127 OK
2) WATER SUPPLY TO HUMIDIFIERS APPEARS TO BE FLOODED INLET. PROVIDE PROOF OF MINIMUM 1' AIR GAP OR PROVIDE CORRECT BACKFLOW PROTECTION NO HIGHER THAN 5' FROM FLOOR LEVEL
05/26/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) IN WALL INSULATION ON HOT PIPING OK
05/20/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WATER TEST WASTE AND VENT THRU ROOF ALL AREAS EXCEPT SUB-STERILE #132, SUB-STERILE 144 AND CLEAN UTIL 127 REQUIRE CITY APPROVED REVISED PLAN FOR LOCATION OF P-15 AND VERIFICATION OF CORRECT STAND PIPE DISTANCE REQUIREMENTS FROM P-TRAP TO WASHER BOX
2) H20 PIPING ALL AREAS EXCEPT SUB STERILE #132 AND 144 AND CLEAN UTIL 127 REQUIRE CORRECT H20 SUPPLY TO CORRECT BACKFLOW DEVICE WITH REVISION CITY APPROVED FOR LOCATION FOR BACKFLOW DEVICE DRAIN TO APPROVED INDIRECT RECEPTOR
3) NEED TO VIEW CLOSET FLANGES PRIOR TO SETTING STOOLS AND CONNECTION OF H20 TO ALL HUMIDIFIERS WITH DRAINS
05/19/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :* WATER TEST WATE & VENT THRU ROOF ( SOUTH EAST QUAD SECTION D) WITH H20 PIPING 120 PSI TEST OK EXCEPT. 1) SUB ST?? # 132 REQUIRES 3/4 H20 TO P-15 WITH CORRECT BACKFLOW PROTECTION & TERMINATION OF DRAIN INTO CORRECT RECEPTOR. PENDING NOTES FROM 5/16 & 5/17. ENTIRE WASTE & VENT SYSTEM IS FULL OF WATER THRU ROOF AT THIS TIME. THIS INSPECTION FOR QUAD D ONLY.
05/17/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* PLEASE NOTE: REVISED & APPROVED PLANS WILL BE REQUIRED FOR ANY CHARGES. PLEASE NOTE SPEC ON INSULATION. PLEASE PROVIDE LOCATION ON PLAN FOR INDIRECT ?? FOR BACK FLOW DEVICES. TO APPROVED LOCATIONS.
05/16/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* SECTION D. SEC P-15 WILL REQUIRE TEST ON TRAP-ALSO SEE SIZE OF WATER OT UNIT. PLAN CALLS FOR 3/4" 1/2" HAS BEEN INSTALLED. ALSO WILL REQUIRE PROPER BACKFLOW PROTECTION FOR FIXTURE AN RP DEVICE MAY BE REQUIRED PROVIDE PROPER INDERECT WATE TO AN APPROVED RECEPTOR. GAS PARTIAL ON GAS TEST OK NEED TO COMPLETE TO?? & COMPLETE PIPING TO WATER HEATER.