Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 4 - NEW CABLES ARRIVED WITH UL LABELS |
|
| 12/01/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK TEMP C OF O SUBJECT TO TABLES | |
| 11/23/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*UL INSPECTOR SCHEDULED FOR MONDAY 11/28/05 | |
| 11/15/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*RECEIVED GENERATOR TEST REPORT | |
| 11/10/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 11/09/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*LABEL SERVICE PER 700.8 VERIFY LISTING LABEL FOR MED GAS HEATERS, AND ALL MEDICAL EQUIPMENT WITH ELECTRICAL CONNECTIONS FILL UNUSED OPENINGS IN CONTROL CABINET BOND DOOR OPERATOR SWITCH PER 517,13 AND 517.82 GROUND LIGHT HARDWARE |
|
| 11/07/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK TEMP POWER FOR TEST OK 0 POLE HEADS OK PVC CONDUIT TO HOUSE PANEL RECEIVED LETTER FOR TORQUE RECEIVED CHECK # 20900 FOR 108.00 AFTER HOURS INSPE |