Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/15/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The fixtures are not per plans and specifications.| 250* ANY NEWLY INSTALLED OR RELOCATED DROP IN FIXTURES MUST BE FITTED WITH SEISMIC WIRES ( CATTY CORNER) AND SCREWED TO GRID-CENTER OF FIXTURES |
|
| 03/03/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR RECEPTION AREA OK TO COVER 5TH FLOOR ABOVE CEILING OK TO COVER. | |
| 02/09/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* NOT READY CANCELED BY CONTRACTOR | |
| 02/08/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*1) VDV CABLEING TO BE IS PER 725.2, 760.2, 800.2 AND 725.6, 760.6, 800.6 2) FINISH RELOCATED LIGHTS. OK CONDUITS AND EXISTING LIGHTS PHASE I EXCEPT AS NOTED |