Permit: T04CM04762

Parcel: 137053190


Addresses:

5211 S 13TH AV #01

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/08/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
03/07/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
FLASHINGS REQUIRED AT ROOF PENETRATIONS
CHINA BOWL CAPS REQUIRED
USE CLEANOUT PLUGS DESIGNED TO ACCEPT SCREW
03/06/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE LISTING FOR BUILT IN BYPASS FEATURE FOR PRESSURE REDUCER AT WATER SERVICE OR PROVIDE EXPANSION TANKS AT WATER HEATERS.
2. PROVIDE LONG RADIUS DRAINAGE FITTING FOR SINK AIR ADMITTANCE VALVE BELOW FLOOD RIM OF FIXTURE.
3. PROVIDE PERMANENT SIGNAGE IN ELECTRICAL PANELS FOR PLASTIC WATER PIPING IN BUILDING.