Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/10/2006 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 01/31/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BONDING JUMPERS TO BE AS PER 250.10 AND 250.66 2) LUG TO HAVE SURFACE CONTACT FOR BONDING 3) NEED REJECTION PINS AND FUSES 4) LABEL BREAKERS HOUSE PANEL 5) NEED NEUTRAL AT DISCONNECT 6) CHASE NIPPLE NOT LISTED FOR USE WITH LB-USE APPROVED FITTING |