Permit: T04CM04754

Parcel: 110035350

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM04754

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/10/2005 FRAMING Approved IVRS - Inspection :*
02/08/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RECALL WHEN STUCCO MESH IS COMPLETED
2) REAR PORCH MUST BE FASTENED 6" ON CENTER TOP PLATES
02/07/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TO BE APPROVED WHEN STUCCO MESH IS COMPLETED BACK PORCH
02/04/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLUSH NAIL GARAGE SHEAR
2) PROVIDE STUDS 16" ON CENTER KITCHEN CABINET WALLS
3) FASTEN MESH 6" ON CENTER AT TOP PLATE AT PORCH (REAR)
4) NAIL PROTECT GARAGE DOOR TOP PLATE NORTH
5) MICROWAVE OUTLET MUST TERMINATE IN BOX
6) CABLE WIRE BY MAIN SERVICE EXPOSED
7) PROVIDE CLEARANCE AT PEX LINE FROM CANS IN KITCHEN
8) NAIL PROTECT BATH 2" VTRS
9) GROUND FOR TEMP POWER ?
02/02/2005 FRAMING Not ready for Inspection IVRS - Inspection :*