Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T04CM04751
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2004 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 12/29/2004 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) KITCHEN FEED THRU WALL 2) FRONT COUNTER IS NOT READY |
|
| 12/23/2004 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALLATION OF MC CABLE DOES NOT MEET CODE REQUIREMENTS |
|
| 12/22/2004 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) THE MC CABLE IS NOT PROPERLY INSTALLED, SUPPORTED OR TERMINATED 2) BOXES ARE MISSING K-O SEALS 3) SEE MANUFACTURERS INSTRUCTIONS AND REFER TO NEX ART 332-334 |
|
| 12/08/2004 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :*/U/G - UNDERSLAB PVC CONDUIT-OK TO COVER |