Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2005 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/31/2005 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 01/28/2005 | PLUMBING - ROUGH, SOIL | Cancelled | ||
| 01/14/2005 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO APPROVED PLAN ON SITE 2) NO ISOMETRIC DRAWINGS 3) THE UNAPPROVED PLAN SHOWS 2" FOR FLOOR SINKS TYING INTO A 4" EXISTING. THE EXISTING OS A 2" NOT 4". 4) THE WATER HEAD TEST FOR ALL THE 2" DWV TO FLOOR DRAINS, OVERHEAD (ABOVE CEILING) VENTS AND VENT STACKS IN WALLS IS OK BUT... YOU MAY NOT COVER PIPE IN SOIL UNTIL PAPER PLANS ARE ON SITE AND INSPECTION APPROVED. |