Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK FINAL | |
| 01/06/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)USE APPROVED METHOD FOR SUPPORTING TRACK LIGHTING - T-BAR STAIPS AND TILES NOT APPROVED. 2)SUPPORT LIGHT FIXTURE BOXES WITH SUPPORT WIRES. 3)LISTED FIXTURE WHIPS NOT APPROVED FOR PERMANENT WIRING METHOD 4)CORD NOT APPROVED TO PASS THROUGH OR PLUG IN ABOVE CEILING 5)CLOSE JUCNTION BOX 6)SUPPORT CONDUIT ABOVE PANEL WITHIN 3' & TIGHTEN LOOSE FITTINGS. FILL UNUSED OPENINGS/REMOVE UNUSED FITTING 7)FILL UNUSED OPENING IN JUNCTION BOXES 8)VDV CABLING TO BE AS PER 725.6 & 800.6 |