Permit: T04CM04730

Parcel: 140376470


Addresses:

6910 S HARRIER LP

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/15/2005 FRAMING Approved IVRS - Inspection :*
04/14/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1, 8, 11, AND 12 FROM 4/12/05 NOT COMPLETE
04/12/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) STUCCO LATH NOT COMPLETE AT GARAGE FRONT AND PATIO
2) W/H T & P LINE BEHIND STUCCO-MOVE
3) ANCHOR BOLTS MISSING AND LOOSE
4) CONNECT SHEAR WALL WITH 12 A35 CLIPS PER S-2
5) DUCT BOOT NOT IN L/R
6) PLUMBERS METAL TAPE NOT ALLOWED TO SUPPORT D.W.V.
7) A7H HANGERS NOT NAILED
8) TUB NOT VENTED ABOVE DRAIN CENTER LINE
9) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE
10) SOME INCORRECT HANGERS INSTALLED USE THA 218-2 AND LUS26-2
11) PROVIDE 1" CLEARANCE AT WATER HEATER VENT (ROOF)
12) FLOOR SHEATHING LOOSE
13) NAIL 2ND FLOOR PER PLAN
14) FIRE STOP GARAGE/BEDROOM WALL
15) STOPPED INSPECTION-TO MANY ITEMS