Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/06/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A/C CONDENSOR BLOCKS ACCESS TO DISCONNECT. YOU MUST PROVIDE A 30" X 30" OBSTRUCTION FREE WORK AREA AT FRONT DISCONNECT. THIRD FAILURE 2) STUCCO LATH DAMAGED AT S.W. CORNER |
|
| 05/05/2005 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) A/C CONDENSOR BLOCKS ACCESS TO DISCONNECT 2) 30" X 30" OPEN SPACE REQUIRED IN FRONT OF DISCONNECT |
|
| 05/03/2005 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :*/ 1) 14 GUAGE WIRE NOT ALLOWED ON 20 AMP BREAKER. 2) DOUBLE LUGGING OF CIRCUIT BREAKERS NOT ALLOWED. 3) FILL OPEN K.O. IN SERVICE PANEL. 4) A/C CONDENSOR BLOCKS ACCESS TO DISCONNECT. 5) MAX ALLOWED A/C FUSE IS 35 AMP - 40 AMP IS INSTALLED. 6) GARAGE OUTLET HOT GROUND REQUIRED. 7) PENISULA GFCI NOT INSTALLED. |