Permit: T04CM04699

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/03/2006 ELECTRIC - ABOVE CEILING Approved
03/29/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FIRE ALARM WIRING NEEDS TO BE SUPPORTED TO STRUCTURE AND OFF GRID AND OTHER EQUIPMENT.
2. FINISH WIRING IN CEILING.
OK TO COVER CEILING AFTER CORRECTIONS.
03/27/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CALL WHEN WIRING IS COMPLETE IN CEILING - FIRE ALARM AND OTHER LOW VOLTAGE SYSTEMS.
03/08/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*