Permit: T04CM04695

Parcel: 11615088L

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
12/02/2005 PLUMBING - INTERMEDIATE Approved N/H DWV,IN WALLS , AND OVERHEAD TO P.O.C OK
COPPER IN WALLS OK
OK TO INSULATE HOT.
DIALYSIS DRAINS MAY NOT BE COMBINED
11/21/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*N/H DWV & COPPER SOUTH HALF OK TO COVER EXCEPT R.O WATER
10/24/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*WALKED THROUGH THE 3RD FLOOR WITH G.C BEGINNING PHASE TWO.
08/22/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/22/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RM 4107 USE DWV DRAINAGE FITTING ON TRAP ARM VENT WILL REQUIRE ADDITIONAL HANGERS
2) ROOM 4102 ONLY HAS 1/2" HOT FOR TWO SHOWERS AND A LAVATORY - PER PLAN - PLEASE CLARIFY WITH ACURATE REDLINES - OK TO COVER
3) OK TO COVER AREAS AS DISCUSSED WITH G.C.