Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM04695
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/02/2005 | PLUMBING - INTERMEDIATE | Approved | N/H DWV,IN WALLS , AND OVERHEAD TO P.O.C OK COPPER IN WALLS OK OK TO INSULATE HOT. DIALYSIS DRAINS MAY NOT BE COMBINED |
|
11/21/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*N/H DWV & COPPER SOUTH HALF OK TO COVER EXCEPT R.O WATER | |
10/24/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*WALKED THROUGH THE 3RD FLOOR WITH G.C BEGINNING PHASE TWO. | |
08/22/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/22/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RM 4107 USE DWV DRAINAGE FITTING ON TRAP ARM VENT WILL REQUIRE ADDITIONAL HANGERS 2) ROOM 4102 ONLY HAS 1/2" HOT FOR TWO SHOWERS AND A LAVATORY - PER PLAN - PLEASE CLARIFY WITH ACURATE REDLINES - OK TO COVER 3) OK TO COVER AREAS AS DISCUSSED WITH G.C. |