Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM04695
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* NOTE: DUE TO HOSPITAL OPERATIONS, A VISUAL INSPECTION OF THE EMERGENCY SYSTEM (NO LOAD TEST) MADE AT THIS TIME. THE HOSPITAL CONDUCTS REGULAR TEST TO THIS SYSTEM. |
|
01/25/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CORRECTLY IDENTIFY ALL OUTLETS, PANELS AND PANEL DIRECTORIES 2) INSTALL K.O. AND BREAKER BLANKS AS NEEDED 3) INSTALL BUSHINGS FOR #4 AND LARGER WIRE 4) IDENTIFY FUTURE CKT'S IN PANEL 5) GROUND J-BOXES FOR PANEL 4EE1 |
|
12/30/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/12/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS AND CEILING IN RM 4108 |
|
12/06/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*BOX'S NEED TO BE PROPERLY SUPPORTED REMOVE ALL EXISTING BOX'S AND WIRING THAT WILL NOT BE USED. INSTALL ALL MUD RINGS,STRAP RACEWAYS |
|
11/22/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROOMS #4101M, Q, O, L, M, G, H, I1, I2, J AND X HARD LIDS AND WALLS |
|
08/19/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) KITCHEN AREA 4107, 4144, 4106, 4102 OK WALLS-PHASE ONE 2) PLEASE MAKE AN EFFORT TO SUPPORT EXISTING CONDUITS, CABELING, NOT SUPPORTED TO CODE IS A POTENTIAL HAZARD, NOT IN SCOPE OF WORK FOR CONTRACTOR ON SITE. THE OWNER WILL BE RESPONSIBLE. THERE WILL BE NO FINAL APPROVAL OF JOB UNTIL THIS IS ADDRESSED |