Permit: T04CM04695

Parcel: 11615088L

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/26/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
NOTE: DUE TO HOSPITAL OPERATIONS, A VISUAL INSPECTION OF THE EMERGENCY SYSTEM (NO LOAD TEST) MADE AT THIS TIME. THE HOSPITAL CONDUCTS REGULAR TEST TO THIS SYSTEM.
01/25/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CORRECTLY IDENTIFY ALL OUTLETS, PANELS AND PANEL DIRECTORIES
2) INSTALL K.O. AND BREAKER BLANKS AS NEEDED
3) INSTALL BUSHINGS FOR #4 AND LARGER WIRE
4) IDENTIFY FUTURE CKT'S IN PANEL
5) GROUND J-BOXES FOR PANEL 4EE1
12/30/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/12/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS AND CEILING IN RM 4108
12/06/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*BOX'S NEED TO BE PROPERLY SUPPORTED
REMOVE ALL EXISTING BOX'S AND WIRING THAT WILL NOT BE USED.
INSTALL ALL MUD RINGS,STRAP RACEWAYS
11/22/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ROOMS #4101M, Q, O, L, M, G, H, I1, I2, J AND X HARD LIDS AND WALLS
08/19/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) KITCHEN AREA 4107, 4144, 4106, 4102 OK WALLS-PHASE ONE
2) PLEASE MAKE AN EFFORT TO SUPPORT EXISTING CONDUITS, CABELING, NOT SUPPORTED TO CODE IS A POTENTIAL HAZARD, NOT IN SCOPE OF WORK FOR CONTRACTOR ON SITE. THE OWNER WILL BE RESPONSIBLE. THERE WILL BE NO FINAL APPROVAL OF JOB UNTIL THIS IS ADDRESSED