Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM04693
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/23/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) SINGLE CONDUCTOR TO PANEL TO BE INSTALLED IN APPROVED RACEWAY-EXISTING CONDITION UNSAFE 2) BRING BOXES FLUSH TO DRY WALL FACE 3) FIXTURES RELOCATED TO HAVE SUPPORT WIRES AND ATTACHED TO GRID 4) WE HAVE UN-SUPPORTED NM CABLE ABOVE CEILING |
|
11/22/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |