Permit: T04CM04663

Parcel: 12810082B


Addresses:

5340 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM04663

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/31/2005 MECHANICAL - FINAL Approved
03/25/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) FINISH CORRECTIONS FROM PREVIOUS INSPECTION
2) OK FOR TEMP C OF O
03/24/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* NEED TO TEST DUCT SMOKE DETECTORS. PROVIDE PROPER SIZE BREAKERS FOR CONDENSORS. PERMANENTLY IDENTIFY CONDENSERS & FANS O N ROOF. EF-2 NOT INSTALLED PER PLAN. PROVIDE NECESSARY SENSORS & CONTROLS INTERLOCKED WITH AC-1. REVISE PLANS. PROVIDE FRESH AIR INTAKES ON A/C 1,3 & 4