Permit: T04CM04663

Parcel: 12810082B


Addresses:

5340 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
02/17/2005 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
02/15/2005 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :* CHECK YOUR GAS PIPING PLAN IT REQUIRES 1 1/4" PIPE TO NEW POWER GENERATOR ON ROOF. YOU HAVE 1" INSTALL PER YOUR APPROVED PLANS CLOSET RINGS OK
02/11/2005 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999* PROVIDE CORRECT HANGERS FOR ABS HORIZONTAL PIPING. PROVIDE CORRECT HANGERS FOR H20 PIPING AT WATER HEATER AREA.
02/10/2005 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*