Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/21/2005 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DRYER DUCT CONDUCTOR PIPE USED ( OVAL DOWN SPOUT ?) IS TO SMALL. DRYER DUCT MINIMUM IS 4" SEE FITTING USED ON FLOOR PLATE. USE LARGE SIZE OVAL FOR DRYERS 2) PROVIDE PLASTER GRD. MATL. ON SUPPLY TOPS. RAW EDGE NOT ACCEPTABLE 3) PROVIDE BLOCKING, EXH. FAN HOUSINGS 4) CONDENSATE DRAINS ? WOULD SUGGEST RUNNING NOW UNDER ROOF, DOWN STUD SPACE TO DAY LIGHT 5) WATER HEATER VENT, CONTINUE B-1 VENT BELOW CEILING INTO ROOM. NO SINGLE WALL CONNECTOR PIPE AND ABOVE CEILING. WHERE IS COMBUSTION AIR DUCTS FOR WATER HEATER ROOM |