Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM04662

Parcel: 115181240


Addresses:

535 W HELEN ST #01

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
05/01/2005 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
04/21/2005 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DRYER DUCT CONDUCTOR PIPE USED ( OVAL DOWN SPOUT ?) IS TO SMALL. DRYER DUCT MINIMUM IS 4" SEE FITTING USED ON FLOOR PLATE. USE LARGE SIZE OVAL FOR DRYERS
2) PROVIDE PLASTER GRD. MATL. ON SUPPLY TOPS. RAW EDGE NOT ACCEPTABLE
3) PROVIDE BLOCKING, EXH. FAN HOUSINGS
4) CONDENSATE DRAINS ? WOULD SUGGEST RUNNING NOW UNDER ROOF, DOWN STUD SPACE TO DAY LIGHT
5) WATER HEATER VENT, CONTINUE B-1 VENT BELOW CEILING INTO ROOM. NO SINGLE WALL CONNECTOR PIPE AND ABOVE CEILING. WHERE IS COMBUSTION AIR DUCTS FOR WATER HEATER ROOM