Permit: T04CM04659

Parcel: 119010790


Addresses:

316 W 43RD ST #01

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/26/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/25/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*GAS SHUT OFF VALVES MUST PRECEDE THE FLEX CONNECTOR.
PROVIDE ROOD JACKS ON ALL ROOF PENETRATIONS-ELEC, GAS , CONDENSATE
DO NOT USE WHITE WIRE TO POWER A/C UNITS, TAPE BOTH ENDS W/BLACKTAPE. TIGHTEN LOOSE ELEC. FITTINGS. RECALL FOR INSPECTION.