Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/09/2004 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 10/22/2004 |
BUILDING - FINAL |
|
Not ready for Inspection |
1) INSTALL LUG KITCHEN IN SERVICE PANEL, ONLY ONE WIRE PER LUG 2) NEED COOLER ELECTRIC FINISHED, ARIZ BOX REQUIRED 3) LABEL SMALL PANEL AT SERVICE FOR, 15 AMP, 30 AMP 4) 30 AMP CIRCUIR STRANDED WIRE TO DRYER, STRANDS CUT AT BOTH ENDS 5) NEED SMOKE DETECTORS (BATTERY TYPE IN EACH BEDROOM) |