Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM04641
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* APPROVED | |
02/04/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DUCT SMOKE DETECTOR OK. PROVIDE A FRESH AIR INTAKE ON A/C UNIT. SECURE ELEC. DISCONNECT. ADEQUATELY SUPPORT CONDENSATE DRAIN. 3/8" ID GAS FLEX NOT ADEQUATE FOR 120, 000 BTU | |
02/03/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DUCT SMOKE DETECTOR NOT SHUTTING OF A/C UNIT. |