Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/02/2005 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 02/24/2005 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* PROVIDE A CONDENSATE DRAIN LINE TO MP SINK. PROVIDE A DUCT SMOKE DETECTOR AS PER PLAN |