Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04631
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/12/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*1) MEET WITH STEVE EMERY. HE WILL TAKE CARE OF REMAINING ITEMS. G AND J IN WORKING LETTER FOR WATER HEATER. OK TEMP C OF O PLEASE ROLL BOND OVER | |
04/11/2005 | ELECTRIC - FINAL | Cancelled | ||
04/11/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL & REVISE CIRCUIT DIRECTORIES. 2) LABEL DISCONNECTING MEANS FOR WALKIN FAN COILS. 3) TIGHTEN LOOSE SEALTITE FITTINGS -ROOF. 4) FINISH ITEMS 1,4,& 5 PREVIOUS INSPECTION. |
|
04/08/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE OR FLUSH AT COMBUSTIBLES NEED AN APPROVED EXTENDER RING. 370-20/314.20 2) USE FITTINGS APPROVED FOR M/C CABLE. 3) FILL UNUSED OPENINGS IN BACK OF PANEL. 4) SEAL WALKING BOX RACEWAYS AS PER 300.7 |
|
04/07/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*AP. PREVIOUSLY BY M. CAPISTRANO. OK TO CLEAR FUEL & TESTING POWER. 1) INSTALL PLASTIC BUSHING AT PANEL FOR 100AMP SUBFEE. 2) INSTALL GROUNDING JUMPER AT GROUNDING BUS BAR 3) INSTALL DISCONNECTING MEANS AT FAN COIL @ A.C UNIT. | |
04/06/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NOT APPROVED. PROVIDE PROOF OF PERMIT AND INSPECTIONS FOR NEW SERVICE METER & MAIN SWITCH | |
04/01/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* A BOND WILL BE NEEDED FOR TEMP POWER FOR TEST |