Permit: T04CM04631

Parcel: 11460019B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/06/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/15/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* 1) SEAL UNUSED OPENINGS IN BOXES. 2) FINISH #1 OF PREVIOUS INSPECTIONS. CHECK ON FINAL.
03/01/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) M/C CABLE TO BE SUPPORTED WITHIN 12" OF BOXES
2) FIXTURES TO BE ATTACHED TO GRID 410.16
3) TERMINATE M/C CABLE TO LIGHT ?
4) PREVENT DIE ELECTRIC CONTACT WITH COPPER PIPING
5) IS EXISTING JUNCTION BOX ACCESSIBLE ?