Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM04631
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
03/15/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SEAL UNUSED OPENINGS IN BOXES. 2) FINISH #1 OF PREVIOUS INSPECTIONS. CHECK ON FINAL. | |
03/01/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) M/C CABLE TO BE SUPPORTED WITHIN 12" OF BOXES 2) FIXTURES TO BE ATTACHED TO GRID 410.16 3) TERMINATE M/C CABLE TO LIGHT ? 4) PREVENT DIE ELECTRIC CONTACT WITH COPPER PIPING 5) IS EXISTING JUNCTION BOX ACCESSIBLE ? |