Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/03/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) GROUND ALL METAL BOXES 2) ALL WIRING MUST TERMINATE IN APPROVED BOXES 3) EXPOSE ALL WIRING 4) NO WATER IN DWV SYSTEM/COPPER LINES OK 5) CAST IRON LEAK NOT ABLE TO TEST 6) SUBMIT REVISION ON PLANS FOR UNDERSLAB WORK TO BE DONE 7) COMPLETE ALL LATH TO WEST WALL 8) OK TO INSULATE ? 9) EXPOSE ALL WASTE VENTS FOR INSPECTION |
|
| 02/28/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) FIRESTOP SOUTH WALL TO CEILING 2) NAIL PROTECT ALL ROMEX UNDER 1 1/4" 3) ELECTRIC NOT COMPLETE ALL ROMEX MUST TERMINATE IN APPROVED BOXES 4) NAIL PROTECT WASTE VENTS 5) NO WATER IN DWV SYSTEM 6) COMPLETE STUCCO LATH TO EAST WALL PRIOR TO INTERMEDIATE INSPECTIONS 7) STOPPED INSPECTION |