Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM04584
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/05/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* THE RUNS OF MC CABLE RUN FIXTURE TO FIXTURE REQUIRES A SUPPORT WIRE AT MID SPAN. SEE NRC ART 330 MC CABLE. 2. NEW RECEPTACLE AT FRONT-MISSING. 3. MARK A/C DISCONNECT WITH POWER SOURCE-PANEL & CIRCUITS. 4. IS DUCT SMOKE DETECTOR W/ ALARM ON PNLA CKT. 20 INSTALLED? CORRECT & RECALL INSPECTION. |