Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/16/2005 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* 1) REVISED PLAN ON SITE OK TO COVER |
| 02/09/2005 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :*1) SOME CORRECTIONS HAVE BEEN MADE BUT NO CHANGE IN THE PLAN. PLEASE READ ALL NOTES FROM 2/08/05 AND COMPLY |
| 02/08/2005 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* 1) PLAN APPROVAL IN ERROR. 2) NO TRAP AT DRAIN TO INTERCEPTOR. 3) NO ?? REQUIRED UPSTREM OF INTERCEPTOR. 4) VERIFY VENT SIZE FOR INTERCEPTOR- PLAN CONFLICTING. 5) PROVICE LISTING FOR AIR ADMITTANCE VALVE TO BE INSTALLED IN AN EXPOSED EXTERIOR LOCATION. 6) 2 WAY CLEAN OUT FITTING IS SUPERFLOUS-PLAN CONFLICTING |