Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2005 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 01/31/2005 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1 SANITARY T FITTING CANNOT BE USED IN HORIZ DRAIN POSITION MUST USE A DIRECTIONAL FITTING APPRVD FOR DRAIN 2 RUBBER COUPLINGS ARE NOT ALLOWED FOR USE UNDER A SLAB 3 TOILET IN S.W. CORNER IS NOT PROPERLY VENTED. VENT MUST CONNECT DOWNSTREAM FROM THE TRAP AND CONNECT ABOVE THE CENTERLINE OF THE SEWER |
|
| 01/19/2005 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* NOT READY |