Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM04561
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/23/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
09/14/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* AIR BALANCE PROGRESSING OK TO CONTINUE TEMP C OF O TO OCCUPY APTS. |
|
09/08/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* NEED A COPY OF THE CERTIFIED AIR BALANCE REPORTS BE SURE TO INCLUDE EXHAUST HOOD & MAKE UP AIR. OK TO CONTINUE TEMP C OF O |
|
09/06/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* EXTEND SEWER VENTS 2' ABOVE FRESH AIR INTAKES. BLOCK & CLAMP GAS PIPE MANAGER'S UNIT. KITCHEN ROOFTOP OK. |
|
09/05/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK TO FILE FOR TEMP C OF O |
|
09/01/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - EXTEND SEWER VENTS 2' ABOVE FRESH AIR INTAKES IF WITHIN 10'. - REPAIR SMASHED & DAMAGED UNITS. - PROVIDE ELEC. DISCONNECTS TO EQUIPMENT. - 1/2" I.D X 36" GAS FLEX NOT ADEQUATE FOR 180,000 BTU - PAINT EXPOSED PVC W/LATEX PAINT. - FLEX CONNECTOR ON TYPE 1 FAN MUST BE LITED FOR THAT APPLICATION. - EXTEND EXHAUST OUTLET TO TOP OF WALL. |
|
08/17/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CHECKED ROOFTOP UNITS SOUTH & WEST BUILDINGS. |