Permit: T04CM04561


Addresses:

370 N PANTANO RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/23/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
09/14/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
AIR BALANCE PROGRESSING
OK TO CONTINUE TEMP C OF O TO OCCUPY APTS.
09/08/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
NEED A COPY OF THE CERTIFIED AIR BALANCE REPORTS
BE SURE TO INCLUDE EXHAUST HOOD & MAKE UP AIR.
OK TO CONTINUE TEMP C OF O
09/06/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
EXTEND SEWER VENTS 2' ABOVE FRESH AIR INTAKES.
BLOCK & CLAMP GAS PIPE MANAGER'S UNIT.
KITCHEN ROOFTOP OK.
09/05/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK TO FILE FOR TEMP C OF O
09/01/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- EXTEND SEWER VENTS 2' ABOVE FRESH AIR INTAKES IF WITHIN 10'.
- REPAIR SMASHED & DAMAGED UNITS.
- PROVIDE ELEC. DISCONNECTS TO EQUIPMENT.
- 1/2" I.D X 36" GAS FLEX NOT ADEQUATE FOR 180,000 BTU
- PAINT EXPOSED PVC W/LATEX PAINT.
- FLEX CONNECTOR ON TYPE 1 FAN MUST BE LITED FOR THAT APPLICATION.
- EXTEND EXHAUST OUTLET TO TOP OF WALL.
08/17/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
CHECKED ROOFTOP UNITS SOUTH & WEST BUILDINGS.