Permit: T04CM04561


Addresses:

370 N PANTANO RD

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/29/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES CLUBHOUSE
08/23/2006 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/16/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/15/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- HANGER STRAPS ON FLEX DUCT FULL 1 1/2" WIDE EVERY 5'.
- PROVIDE REVISION OF PLANS FOR CHANGING DUCT.
- CHECKED GREASE DUCT. OK TO FIRE WRAP.
- PROVIDE FIRE WRAP ON TOP OF HOOD OR 18" CLEARANCE FROM CEILING.
- PROVIDE A CATWALK OR ACCESS DOOR TO CLEANOUT GREASE DUCT.
06/30/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/23/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
DUCT ABOVE PATIOS OK FOR SHEET ROCK.
TRASH CHUTES OK TO COVER.
05/03/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK SHEETROCK 2ND FLOOR EAST BLDG.
03/14/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR PRE ROCK NORTH & EAST BUILDING
02/22/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR PRE SHEETROCK SOUTH BLDG