Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T04CM04561
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
02/08/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* INSTALLATIN OF YARD WATER PER PLAN (CITY APPROVED) C2.1 FROM BACKFLOW DEVICES ON DOWN STREAM SIDE TO 5' FROM BUILDING OK 1. NEED TO SEE CONNECTION TO BUILDING & CONNECTION TO METERS. |
|
02/07/2006 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE APPROVED PLAN FOR WATER PIPING WITH MATERIAL SPECS FOR UNDERGROUND EXTERIOR WATER PIPING 2) 4" C-900 IS INSTALLED FROM METER LOCATION TO 3" PVC SCHEDULE 40 AND 2 1/2" AND 1 1/2" PVC SCHEDULE 40 PER C2.1 WITH DUCTILE FITTINGS, RESTRAINTS AND SCHEDULE 80 MIP ADAPTERS AT DUCTILE REDUCERS. WATER TEST IS OK RPB'S ARE INSTALLED AND WILL NEED TO SEE CONNECTION TO METERS. PROVIDE UNDERGROUND APPROVED WIRE NUTS FOR TRACER WIRE 3) NOTE: YOU SHALL HAVE PDEQ APPROVAL TO DISCHARGE FROM BLDG DRAINS INTO BLDG SEWER PRIOR TO ANY RELEASE WITH APPROVED PLANS ON SITE. PDEQ-AUTHORIZATION TO CONSTRUCT AND AUTHORIZATION TO DISCHARGE |
|
02/06/2006 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* |