Permit: T04CM04561


Addresses:

370 N PANTANO RD


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T04CM04561

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2006 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
02/08/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
INSTALLATIN OF YARD WATER PER PLAN (CITY APPROVED) C2.1 FROM BACKFLOW DEVICES ON DOWN STREAM SIDE TO 5' FROM BUILDING OK
1. NEED TO SEE CONNECTION TO BUILDING & CONNECTION TO METERS.
02/07/2006 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVED PLAN FOR WATER PIPING WITH MATERIAL SPECS FOR UNDERGROUND EXTERIOR WATER PIPING
2) 4" C-900 IS INSTALLED FROM METER LOCATION TO 3" PVC SCHEDULE 40 AND 2 1/2" AND 1 1/2" PVC SCHEDULE 40 PER C2.1 WITH DUCTILE FITTINGS, RESTRAINTS AND SCHEDULE 80 MIP ADAPTERS AT DUCTILE REDUCERS. WATER TEST IS OK RPB'S ARE INSTALLED AND WILL NEED TO SEE CONNECTION TO METERS. PROVIDE UNDERGROUND APPROVED WIRE NUTS FOR TRACER WIRE
3) NOTE: YOU SHALL HAVE PDEQ APPROVAL TO DISCHARGE FROM BLDG DRAINS INTO BLDG SEWER PRIOR TO ANY RELEASE WITH APPROVED PLANS ON SITE. PDEQ-AUTHORIZATION TO CONSTRUCT AND AUTHORIZATION TO DISCHARGE
02/06/2006 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*