Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T04CM04561
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2006 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/28/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OVERHEAD IN CEILING SOUTH, EAST, NORTH, BUILDING INCLUDING LAUNDRY OK |
|
04/26/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/21/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 03040 - TIE IN 2 1/2" PVC TO COPPER SUPPLY NORTHWEST LOCATION OK 1. SUPPORT KITCHEN SINK DRAIN ARMS. 2. ALL T&P DRAINS TO BE CORRECTLY SUPPORTED AND GRAVITY DRAIN TO DAYLIGHT. 3. SUPPORT RAIN DRAIN HORIZONTAL PIPING AT 4' INTERVALS 4. EXPOSE GAS PIPING & WATER PIPING IN CEILING OF LAUNDRY |
|
03/29/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CALL IN FOR 03035 INSPECTION FOR INTERMEDIATE ALSO 03035 -- WATER TEST WASTE & VENT THRU ROOF UNITS 105 THRU 114 AND ABOVE OK WATER PIPING SAME UNITS 60 PSI AIR TEST OK IN UNITS ONLY |
|
03/28/2006 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
03/27/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/23/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR INSULATION IN CORRIDOR CEILING. |
|
03/22/2006 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |