Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04561
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/15/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CONDUCTOR TO BE IDENTIFIED FOR UNGROUNDED CONDUCTORS. 2. PLEASE PROVIDE ACCESS FOR EAST ROOF 3. INSTALL ALL LIGHT FIXTURES AS PER PLANS 4. FINISH CHIMES 5. SUPPORT VDV CABELING (NEW) IN COMMUNITY CENTER |
|
09/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* THERE IS NO ROOF ACCESS TO EAST BUILDING FOR INSPECTION. OK SOUTH BUILDING OK EAST BUILDING EXCEPT ROOF |
|
09/13/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK LOUNGE OK ELEVATOR SOUTH OK LAUNDRY 1. LABEL PANELS 2. DISCONNECTING MEANS FOR WATER HEATER & FAN COILS 3. FILL UNUSED OPENING IN LIGHT BARS 4. FINISH EM LIGHTING MIDDLE STAIRWELL OUTSIDE. *RECEIVED CHECK #24838 FOR $108.00 |
|
09/12/2006 | ELECTRIC - FINAL | Partial Approval | ROOF 1. TIGHTEN LOOSE FITTINGS 2. LABEL DISCONNECTS 3. PLEASE VERIFY LISTING FOR FITTINGS BLDG 1. EM LIGHTING NOT WORKING 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RING 314.20 3. NEED DISCONNECTING MEANS FOR FAN COIL. OK BOTTOM FLOOR EXCEPT AS NOTED SOUTH RECEIVED CHECK #24835 FOR $108.00 |
|
09/11/2006 | ELECTRIC - FINAL | Partial Approval | 1. LOCKOUT FOR FAN COIL. OK COMMUNITY CENTER & MANAGER UNIT OK 2ND FLOOR SOUTH RECEIVED CHECK #24852 FOR $108.00 |
|
09/08/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED PANEL DIRECTORY'S 408.4 2. USE ADEQUATE SUPPORTS ABOVE PANEL 3. MAKE UP FIRE PLACE 4. DISCONNECTING MEANS FOR WATER HEATER 5. FINISH ROOF *CHANDELIERS ON BACK ORDER |
|
09/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |