Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/10/2005 | FRAMING | Cancelled | IVRS - RI canceled | |
| 02/10/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPLACE OVER NOTCHED 2 X 6 STUD AT MASTER BATH 2) NO TEST ON DWV'S 3) PROVIDE 12" CLEARANCE FROM CAN LIGHTS TO WATER LINES 4) SHIM HEADERS 5) PLUMBERS TAPE NOT ALLOWED TO SUPPORT AB'S |
|
| 02/09/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NEED H20/DWV TESTED 2) FIRE STOP FIREPLACE CHASE 3) 12" PEX TO CAN LIGHTS KITCHEN 4) F/BLK AT DRYER VENT |
|
| 01/24/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS/PERMIT 2) MUST COMPLETE LATH PRIOR TO REQUESTING INSPECTION FOR INTERMEDIATES |
|
| 12/01/2004 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |