Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* 1) NOTE: AT REAR PORCH/BEDROOM NEED SHEAR TRANSFER DETAIL, VAULTED ROOF TO FLAT CEILING EACH SIDE OF SHEARWALL |
|
| 01/24/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INCOMPLETE-ITEMS NOT COMPLETE |
|
| 01/20/2005 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY, CANCELLED PER CONTRACTOR |
|
| 01/18/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE LAST INSPECTION 2) SHEAR PANELS IN GARAGE NOT PER DETAIL 3) NO TRUSS CALCS 4) NO ACCESS TO ROOF |
|
| 01/10/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS NOT CORRECTED 2) STOPPED INSPECTION |
|
| 01/07/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SW7 REQUIRES 3"-12" NAILING WITH 5/8" ANCHOR BOLTS AT 24" CENTERS 2) STRAP PLUMBING EXTERIOR BOTTOM PLATES 3) STUDS EXCESSIVELY SPLIT-DAMAGED ARSP4'S 4) PATIO BEAM TO POSTS REQUIRE EPC'S ON 2 (2 X 6) STUDS 5) OPTIONAL TRUSSED PATIO REQUIORES 4 X 10 BEAM WITH EPC'S AT BEARING 6) 8D'S AT 6" ON CENTER SPACING REQUIRED THROUGH ROOF SHEATHING INOT 2 X BLOCKS AT TRUSS BEARING 7) INSTALL A.35'S BOTTOM CHORD TRUSSES AND 16D TOE NAILS TO BEARING AT SW3 AT 24" ON CENTER SPACING 8) NEED LADDER TO INSPECT ROOF 9) SHEARWALL TRANSFER INCOMPLETE 10) STOPPED INSPECTION |